Brand Name : Lensen
Model Number : LS-RAI04
Place of Origin : China
MOQ : 2pcs
Price : Negotiation
Payment Terms : T/T, Western Union,
Supply Ability : 6000pcs/month
Delivery Time : 2-7days
Packaging Details : standard carton
Power output : 1W
Channels : 4AI
Input type : 0-5V or 0-20mA or 0-10V
Distance : 2km
Application : wireless sensor
Technology : RF or Lora
RTU Wireless Control Module
Wireless Analog Input Module 4-20mA Signal Wireless Transmission Modbus RTU
 
 LS-RAI04 4 channels analog input module
 4 channels 4-20mA signal wireless transmission to PLC
 0-5V analog signal wireless transmission
 0-10V analog signal wireless transfer
 2km wireless control in industry automation area
  
 Lensen Wireless RTU features
 - Portable device, DIN-rail mounting for easy installation
 - Isolated inputs
 - LEDs for power supply, communication, input, output status
 - Flexible networking, point to point or point to multipoints
 - DIP to change different modes
 - Different types of I/O, DI, DO, AI, AO are available
 - I/O expandable
 - Short delay time
 - Easy handing on RS485 network, support Modbus RTU protocol
 - Support on-line upgrade. Can configure by customer in setting mode
  
 Paramaeters
| Frequency | 433MHz or 450MHz or 470MHz or 868MHz/915MHz or 4G | 
| Power output | 1W | 
| Products | 4AI | 
| Input type | 4-20mA or 0-5V or 0-10V | 
| Output type | 4-20mA or 0-5V or 0-10V | 
| Resolution ratio | 24 bit | 
| Accuracy | ±0.02% | 
| Power supply | 9-36V DC usually use 24V DC | 
| Interface | RS-485 | 
| Channel No. | 15ch default, can program via DIP switch | 
| Antenna | Sucker antenna with 1.5m cable | 
| Working temperature | -35 °C~+75 °C industrial | 
| Working humidity | 10%-90% relative humidity, no condensation | 
| Dimension | 115×90×40(mm) | 
| Fix way | Standard 3.5 inch industrial DIN guild rail | 
 
  
Advantage of wireless solution
 - No wires to bury or maintain, no need to drill holes on wall
 - Reliable communication in all direction,any terrain, regardless of hills, walls, trees
 - Cost saving in installation and maintenance
 - Radio/Lora based, no need internet and monthly fee, full ownership of the system
 - 4G based, high speed, no distance limit
 
 Modbus RTU communication and corresponding value 
  
 Register types:
| Register types | Read command |  			 Write command  |  			Power off | Function | 
| Hold register | 0x01 |  			 Input --not support  |  			Not keep | Can read input value | 
| 0x03 | 
 
 A. Hold register
 1. Analog input value: 0x0008~0x000B
 2. Analog output value: 0x0048~0x004B
  
 B: How to read
 Hold register: can read 4 analog input or control 4 analog output at one time
  
 Register control way
  
| AI/AO | IC |  			 Read/  |  			Function ID | items support | ||
| No. | IC Type | PLC ID | Modbus ID | |||
| AI1 | Hold register | 40009 | 8 | Read | 03 | 2AI/4AI | 
| AI2 | Hold register | 40010 | 9 | Read | 03 | |
| AI3 | Hold register | 40011 | 10 | Read | 03 | 4AI | 
| AI4 | Hold register | 40012 | 11 | Read | 03 | |
| AO1 | Hold register | 40073 | 72 | Read/write | 03/06 | 2AO/4AO | 
| AO2 | Hold register | 40074 | 73 | Read/write | 03/06 | |
| AO3 | Hold register | 40075 | 74 | Read/write | 03/06 | 4AO | 
| AO4 | Hold register | 40076 | 75 | Read/write | 03/06 | |
 
 About value calculation
  
 Analog input
 Our analog module’s max measure range value is : 0X7FFF
 1. Directly measure current and voltage
 Exact value=value you read/0x7FFF*max range
 For example: to read the 1st passage of module’s (with max range of 0-20mA) input value
 Register 0x0008(analog input of the 1st passage)
 Feedback: 0x3801
 Current value: (0x3801/0x7FFF)*20mA=8.7509mA
  
 2. To measure sensor’s value(4-20mA, 0-6 meter level sensor)
 If feedback value is less than 6554, level value is 0
 If feedback value is bigger than 6554, level value=(value read-6554)/(32767-6554)*measure ranges
 For example: feedback value is 0X3801, then corresponding level value is: ((0X3801-6554)/26213)*6 meter=1.7815 meter
  
 Analog output
 Analog module’s max measure range is: 0x7FFF
 Directly control output current and voltage
 Write register value=current or voltage value/measure range*0x7FFF
 For example: to control the 1st passage of analog module whose max measure range is 0-20mA
 Register 0x0048 (analog output of the 1st passage)
 To write register value:(8.75/20mA)*0X7FFF =14336=0x3800
  
  
  
 
  
  
  
  
  
| 
                                             | 
                